5. Connect ground to terminal and power to terminals L/+ and N/- using wiring tool in the
manner shown below at right.
① L/+
② N/-
③ Protective Earth (PE)
AC connection DC connection
Power: 100 to 240 V AC, 47 to 63 Hz
Power: 19.2 to 28.8 V DC
6. Close and latch power supply terminal protection cover.
7. Tighten cable gland.
5.2.4.7 Connecting the power supply (with DSL)
1. Open enclosure lid, unscrew power supply terminal protection cover screw, and remove
protection cover.
2. Remove blind plug and fit cable gland.
Connecting
5.2 Connecting MASS 2100/FC300
MASS 2100 & FC300 (FCT030)
76 Operating Instructions, 06/2017, A5E39789040-AA