Siemens FC300 - Special Conditions for Safe Use

Siemens FC300
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MASS 2100
ATEX Certificate : DEMKO 03 ATEX 135252X
Sitrans FC MASS 2100 can be used in zone 0, 20
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
IECEx Certificate : IECEx ULD 17.0029
Sitrans FC MASS 2100 can be used in zone 0, 20
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
Canada Certificate. UL E232147
Sitrans FC MASS 2100 can be used in zone 0, 20 and Class I+II+III Division 1. Grp. A,B,C,D,
E, F, G
Class I+II+III Division 1. Grp. A,B,C,D, E, F, G.
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
US Certifikate: UL E232147
Sitrans FC MASS 2100 can be used in zone 0 and Class I Division 1.
Class I+II+III Division 1. Grp. A,B,C,D, E, F, G.
AEx ia IIC T6…T3 Ga
AEx ia IIIC T135°C…T180°C Da
2.4.5 Special conditions for safe use
Special conditions for safe use
In general, it is required that:
The transmitter electronic compartment shall not be opened when energized and when an
explosive gas or dust atmosphere may be present.
The terminal compartment may be opened when an explosive gas or dust atmosphere may
be present at any time. Access power terminals by lifting the cover only when de-energized.
Appropriate cable connectors are used.
Substitution of components may impair Intrinsic Safety.
Safety notes
2.4 Use in hazardous areas
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 23

Table of Contents

Related product manuals