Configure the dosing function as follows:
1. Basic dosing parameters common for all recipes in menu 2.5 "Dosing"
Select valve control functionality at parameter "Dosing Mode"
Select measured process value for dosing at parameter "Process Values"
2. Individual recipe(s) in menus 2.5.4 to 2.5.8 as required
Setup dosing name, amount, unit and compensation
Select valve control sequence
Select fault handling configuration
3. Output(s) in menu 2.4 "Inputs/Outputs" (see table below).
4. Input for dosing control in menu 2.4 "Inputs/Outputs"
8.8.1 Dosing control configuration
Dosing control includes valve control (discrete/analog) and fault handling. The valve control is
done using channels 2, 3 and 4. Dosing control can be configured to:
One on/off valve
Two on/off valves
Control valve
One on/off valve
Use one Signal or one Relay output to control the one-stage dosing. Set the Operating Mode
of signal output to Status. Assign Status Mode to control the Primary Valve. A Signal Input can
be assigned to start the dosing.
Two on/off valves
Use two Signal or two Relay outputs to control the two-stage dosing. Set the Operating Mode
of signal output to Status. Assign one Status Mode to control the Primary Valve and the other
to control the Secondary Valve. A Signal Input can be assigned to start the dosing.
Control valve
Use one Signal output to control the Control valve. Assign the Operating Mode to Current
Output. A Signal Input can be assigned to start the dosing.
Process Values
The following process values can be used for dosing control:
Mass flow
Volume flow
Functions
8.8 Dosing
MASS 2100 & FC300 (FCT030)
156 Operating Instructions, 06/2017, A5E39789040-AA