WARNING
Unsuitable connecting parts
Risk of injury or poisoning.
In case of improper mounting hot, toxic and corrosive process media could be released at
the connections.
Ensure that connecting parts (such as flange gaskets and bolts) are suitable for connection
and process media.
4.2.1.3 Mounting the sensor
Install the sensor in well-supported pipelines in order to support the weight of the
flowmeter.
Figure 4-4 Avoid vibrations
Center the connecting pipelines axially in order to assure a stress-free installation. The
flowmeter must not be used to bring the rest of the pipework into line; make sure the
pipework is correctly aligned before inserting the flow sensor.
Install two supports or hangers symmetrically and stress-free on the pipeline in close
proximity to the process connections.
Note
Handling
Never lift the flowmeter using the housing, that is always lift the sensor body.
Avoid vibrations
Make sure that any valves or pumps upstream of the sensor do not cavitate and do not
send vibrations into the sensor.
Decouple vibrating pipeline from the flow sensor using flexible tube or couplings.
Installing/mounting
4.2 Installation instructions
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 45