11.10 Approvals
Table 11-28 Certificates and approvals
Description Specification
ATEX
FCT030 transmitter (can be installed in Zone
1 for gas and Zone 21 for dust):
Certificate SIRA 11ATEX1342X:
II 2(1) GD
Ex db eb [ia Ga] IIC T6 Gb Ta = -40°C to +60°C
Ex tb [ia Da] IIIC T85°C Db
IECEx
FCT030 transmitter (can be installed in Zone
1 for gas and Zone 21 for dust):
Certificate: IECEx SIR 11.0150X
Ex db eb ia [ia Ga] IIC T6 Gb Ta = -40°C to
+60°C.
Ex tb [ia Da] IIIC T85°C Db
CSA
Ex Canada: FCT030 transmitter (can be installed in Zone 1 for
gas and Zone 20/21 for dust):
Certificate: cCSAus 2508628
Ex db ia [ia Ga] IIC T6 Gb
Ex tb [ia Da] IIIC T85°C Db
For US: FCT030 transmitter (can be installed in Zone 1 for
gas and Zone 21 for dust) and Class I +II+III Group
A, B, C, D, E, F:
Certificate: cCSAus 2508628
Class I, II, III Division 1 Gp A, B, C, D, E, F, G
Class I Zone 1: AEx db ia [ia Ga] IIC T6 Gb
Class II Zone 21: AEx tb [ia Da] IIIC T85°C Db
FC300
ATEX Certificate : DEMKO 05 ATEX 138072X.
Sitrans FC300 can be used in zone 0.
Ex ia IIC T6…T3 Ga
IECEx Certificate: IECEx ULD 17.0030
Sitrans FC300 can be used in zone 0.
Ex ia IIC T6…T3 Ga
Canada Certificate. UL E232147
Sitrans FC300 can be used in zone 0 and Class I
Division 1.
Class I Div. 1 Grp. A, B, C, D.
Ex ia IIC T6…T3 IIC Ga
US Certifikate. UL E232147
Sitrans FC300 can be used in zone 0 and Class I
Division 1.
Class I Div. 1 Grp. A, B, C, DA
AEx ia IIC T6…T3 IIC Ga
Technical data
11.10 Approvals
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 239

Table of Contents