Bidirectional flow across zero with positive scaling
)&
v
v
mA
Kg/h
v
v
v
NJKNJK
P$
P$
P$
P$
① Lower scaling
② Low-flow cut-off
③ Upper scaling
④ Maximum measurement value
⑤ Upper range
⑥ Lower range
⑦ Minimum measurement value
⑧ Lower alarm value
⑨ Measurement range
Current output setting
● Process value = Massflow
● Direction = Bidirectional
● Current Mode = 4-20 mA US
● Upper Scaling = 400 kg/h
● Lower Scaling = -100 kg/h
● Fail Safe Mode = Minimum current
● Low-Flow Cut-Off = 25 kg/h
Functions
8.6 Inputs and outputs
MASS 2100 & FC300 (FCT030)
148 Operating Instructions, 06/2017, A5E39789040-AA