Positive flow across zero with positive scaling
)&
v
v
mA
Kg/h
-100 kg/h
400 kg/h
v
v
v
P$
P$
P$
P$
P$
Lower scaling
Low-flow cut-off
Upper scaling
Maximum measurement value
Upper range
Lower range
Minimum measurement value
Lower alarm value
Measurement range
Current output setting
Process value = Massflow
Direction = Bidirectional
Current Mode = 4-20 mA NAMUR
Upper Scaling = 400 kg/h
Lower Scaling = -100 kg/h
Fail Safe Mode = Maximum current
Low-Flow Cut-Off = 25 kg/h
Functions
8.6 Inputs and outputs
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 147