Table 11-6 Additional error by deviations from reference conditions
Sensor size DI 1.0 DI 1.5 DI 2.1 DI 3 DN4 HP
(DI 2.0)
DN4 C22
(DI 3.0)
DN4 316
(DI 3.5)
DI 6 DI 15
Effect of ambient
temperature
[% / K actual flow‐
rate]
< ±0.003 < ±0.003 < ±0.003 < ±0.003 < ±0.003 < ±0.003 < ±0.003 < ±0.003 < ±0.003
Current: < ±0.005 < ±0.005 < ±0.005 < ±0.005 < ±0.005 < ±0.005 < ±0.005 < ±0.005 < ±0.005
Effect of power sup‐
ply fluctuations
[% of measuring val‐
ue on 1% alteration
from Un]
None None None <0.005% None None None <0.005% <0.005%
Table 11-7 Process media conditions
Sensor size DI 1.0 DI 1.5 DI 2.1 DI 3 DN4 HP
(DI 2.0)
DN4 C22
(DI 3.0)
DN4 316
(DI 3.5)
DI 6 DI 15
Process media tem‐
perature (T
s
) (min to
max)
Standard [°C
(°F)]
-50 °C to + 125 °C (-58 °F to +
257 °F)
-50 °C to
+ 180 °C
(-58 °F to
+ 356 °F)
-40 °C to
+ 115 °C
(-40 °F to
+ 239 °F)
-40 °C to + 115 °C
(-40 °F to + 239 °F)
-50 °C to + 180 °C
(-58 °F to + 356 °F)
High-
temperature
version [°C (°F)]
n/a -50 °C to
+ 180 °C
(-58 °F to
+ 356 °F)
n/a -40 °C to + 180 °C
(-40 °F to + 356 °F)
Process media den‐
sity (min to max) [g/
cm
3
(lb/inch
3
]
n/a 0 ... 2.9 g/cm3 (0 ... 0.105 lb/
inch3)
n/a 0 ... 2.9 g/cm3 (0 ... 0.105 lb/inch3)
Process media
gauge max pressure
316L sensors [bar
(psi)]
800 bar
at 20 °C
640 bar
at 180 °C
(Derat‐
ing is lin‐
ear)
230 bar
at 20°C
(3336
PSI at 68
°F)
100 bar
at 20 °C
(68 °F)
230 bar
at 20°C
(3336
PSI at 68
°F)
n/a n/a 130 bar
(1885
psi)
at
20-180
°C (68
°F-356
°F)
265 bar
at 20°C
(3844
PSI at 68
°F)
130 bar
at 20°C
(1885
PSI at 68
°F)
Process media
gauge max pressure
Hastelloy C22 sen‐
sors [bar (psi)]
n/a 365 bar
at 20 °C
(5294
PSI at 68
°F)
n/a 350 bar
at 20°C
(5076
PSI at 68
°F)
1000 bar
at max
20°C
(14503
psi)
410 bar
(5945
psi)
at
20-180
°C (68
°F-356
°F)
n/a 410 bar
at 20°C
(5946
PSI at 68
°F
200 bar
at 20°C
(2900
PSI at 68
°F)
Technical data
11.2 Performance
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 217