Table 11-14 Relay output
Description Channels 3 to 4
Type Change-over voltage-free relay contact
Load 30 V AC, 100 mA
Functions
Alarm class / NAMUR status
Individual alarms
Table 11-15 Current output (Channel 1)
Description Channel 1
Signal range 4 to 20 mA
Resolution 0.4 μA
Load
Ex i: <470 Ω (HART ≥ 230 Ω)
Non-Ex: <770 Ω (HART ≥ 230 Ω)
Time constant (adjustable) 0.0 to 100 s
Fault current
Measurement range (mA)
Lower fault current (mA)
Upper fault current (mA)
4 - 20 NAMUR
3.8 - 20.5
3.5
22.6
4 - 20 US
4.0 - 20.8
3.75
22.6
Customized fail-safe mode
Last reliable value
Lower fault current
Upper fault current
Fail-safe value
Current value
Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from
each other and ground.
Maximum test voltage: 500 V AC
Cable Standard industrial signal cable with up to 3 twisted pairs with overall screen can be con‐
nected between the transmitter and the control system. Individual pair or overall screen is
optional depending on user requirements.
Voltage range Max. 24 V DC (active)
14 to 30 V DC (passive)
Table 11-16 Current output (Channels 2 to 4)
Description Channels 2 to 4
Signal range 0/4 to 20 mA
Resolution 0.4 μA
Load
Ex i: <470 Ω
Non-Ex: <770 Ω
Time constant (adjustable) 0.0 to 100 s
Technical data
11.5 Outputs
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 221