HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.2.5.7 Empty Tube Detection "Activate empty tube detection.
""On"": Density value below
empty tube limit triggers alarm.
All flow rate values are forced to
zero %.
Off
Off
On
User
2.2.5.8 Empty Tube Limit "Set density value for empty
tube limit.
Density value below limit trig‐
gers an alarm."
500
[kg/m³]
-14000.0 to
14000.0
User
Table B-5 Medium temperature
HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.2.6.1 Units Select unit for displayed temper‐
ature. Unit is not applied at com‐
munication interface.
°C
°C (degrees
Celcius)
°F (degrees
Fahrenheit)
°R degrees
Rankine
K (kelvins)
User
2.2.6.2
Decimal places Define the decimal point for the
process value displayed in the
Local User Interface.
2
Auto
No decimal
place
1
2
3
4
5
6
User
2.2.6.3 Alarm and warning limits
2.2.6.3.1 Upper Limit Alarm Set upper alarm limit. Alarm is
triggered if temperature value is
above the limit.
200
[°C]
-50 to 200 User
2.2.6.3.2 Upper Limit Warning Set upper warning limit. Warning
is triggered if temperature value
is above the limit.
200
[°C]
-50 to 200 User
2.2.6.3.3 Lower Limit Warning Set lower warning limit. Warning
is triggered if temperature value
is below the limit.
-50
[°C]
-50 to 200 User
Default settings
B.3 Standard volume flow
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 279