HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.4.4.17 NAMUR status signal Select one or more NAMUR sta‐
tus signals. The output is active
when one of the selected signals
occurs.
Failure
Function
check
Out of
specification
Maintenance
required
None
User
2.4.4.18 Polarity Set the level of an active signal. Active high level
Active high
level
Active low
level
User
2.4.4.19 On delay Set the time delay between
alarm condition and activating
the output. Allows to ignore tran‐
sient fault conditions
0 s
0 to 100 s
User
2.4.4.20 Off delay Set the time delay between re‐
setting alarm condition and de-
activating the output. Allows to
ignore transient fault conditions
0 s
0 to 100 s
User
1)
: See Sensor dimension dependent default settings (Page 259)
Table B-14 Channel 4 – input/output
HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.4.5.1 Operation Mode
Set the output functionality you
want the channel to operate.
Off
Off
Current output
Frequency
output
Pulse output
Digital output
Digital input
User
2.4.5.2 Change operation mode
2.4.5.3 Active operation
Shows the application possibili‐
ties of your hardware. The kind
of operation depends on the wir‐
ing.
Active
operation not
possible
Active
operation
possible
User
2.4.5.4 Fail-safe activation con‐
dition
Fail-safe becomes active if ei‐
ther the selected process value
is unreliable, or the device
shows "Maintenance alarm".
Invalid process
value
Invalid
process value
Maintenance
alarm
User
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 345