HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.4.6.17 NAMUR status signal Select one or more NAMUR sta‐
tus signals. The output is active
when one of the selected signals
occurs.
Failure
Function
check
Out of
specification
Maintenance
required
None
User
2.4.6.18 Polarity Set the level of an active signal Active high level
Active high
level
Active low
level
User
2.4.6.19 On delay Set the time delay between
alarm condition and activating
the output. Allows to ignore tran‐
sient fault conditions
0 s
0 to 100 s
User
2.4.6.20 Off delay Set the time delay between re‐
setting alarm condition and de-
activating the output. Allows to
ignore transient fault conditions
0 s
0 to 100 s
User
1)
: See Sensor dimension dependent default settings (Page 259)
2)
Process Value is set to Massflow
3)
Process Value is set to Volumeflow
4)
Process Value is set to Density
5)
Process Value is set to Fluid Temperature
6)
Process Value is set to Corrected Volumeflow
7)
Process Value is set to Fraction A % / Fraction B %
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
376 Operating Instructions, 06/2017, A5E39789040-AA