HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.5.7.7.2 Duration time Define the supervision time. An
alarm is raised and valve(s)
closed if dosing time is excee‐
ded.
3600 1 to 360000 User
2.5.7.7.3 Overrun mode Enable or disable dosing
amount supervision. An alarm is
raised and valve(s) closed if dos‐
ing amount is exceeded.
Off
● Off
● On
User
2.5.7.7.4 Overrun value Define the dosing overrun
amount. An alarm is raised and
valve(s) closed if dosing amount
is exceeded.
0 User
Table B-20 Recipe 4
HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.5.8.1 Name Define the name of the recipe.
Switching between recipes is
done in dosing operating view.
User
2.5.8.2 Unit Select unit for the recipe. Unit is
not applied at communication in‐
terface.
Mass flow
kg
● g
● kg
● t
● STon
● T
● oz
● lb
● Custom
User
Default settings
B.6 Dosing
MASS 2100 & FC300 (FCT030)
394 Operating Instructions, 06/2017, A5E39789040-AA