HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.5.9.6.3 Stage 1 Primary Close Define the dosing amount value
to close the primary valve. The
value is in % of defined dosing
amount.
1.00
SL
User
2.5.9.6.4 Stage 2 Secondary
Open
Define the dosing amount value
to open the secondary valve.
The value is in % of defined dos‐
ing amount.
0.20
SL
User
2.5.9.6.5 Stage 2 Secondary
Close
Define the dosing amount value
to close the secondary valve.
The value is in % of defined dos‐
ing amount.
0.80
SL
User
2.5.9.6.6 Fully Closed Current
Level
Define current level to fully close
the analog valve.
0
[mA]
0 to 20 User
2.5.9.6.7 Partially Open Current
Level
Define current level to partly
close the analog valve.
10
[mA]
0 to 20 User
2.5.9.6.8 Fully Open Current Lev‐
el
Define current level to fully open
the analog valve.
20
[mA]
0 to 20 User
2.5.9.6.9 Fully Open Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
[%]
0.0 to100.0 User
2.5.9.6.10 Partially Closed Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
0.0
[%]
0.0 to100.0 User
2.5.9.6.9 Fully Open Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
[kg]
User
2.5.9.6.10 Partially Closed Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.0
[kg]
User
2.5.9.6.9 Fully Open Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
L
User
2.5.9.6.10 Partially Closed Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.00
L
User
2.5.9.6.9 Fully Open Define the dosing amount value
at which the valve will transition
from partial flow to full flow.
0.0
SL
User
2.5.9.6.10 Partially Closed Define the dosing amount value
at which the valve will transition
from full flow to partial flow.
1.00
SL
User
2.5.9.7 Fault Handling
2.5.9.7.1 Duration mode Enable or disable dosing time
supervision. An alarm is raised
and valve(s) closed if dosing
time is exceeded.
Off
Off
On
User
Default settings
B.6 Dosing
MASS 2100 & FC300 (FCT030)
402 Operating Instructions, 06/2017, A5E39789040-AA