166/617
Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
Line no. Operating line
HC1 HC2 HC3
834 1134 1434 Actuator running time
Set the running time of the actuator used with the mixing valve.
Line no. Operating line
HC1 HC2 HC3
835 1135 1435 Mixing valve Xp
The mixing valve's P-band Xp can be adjusted, thereby matching the control behavior
of the valve's actuator to that of the plant (controlled system). The P-band influences
the controller's P-control action.
Line no. Operating line
HC1 HC2 HC3
836 1136 1436 Mixing valve Tn
The mixing valve's integral action time Tn can be adjusted, thereby matching the
control behavior of the valve's actuator to that of the plant (controlled system). The
integral action time influences the controller's I-control action.
A
ctuator running time
Mixing valve Xp
Mixing valve Tn