Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
6.21.3 DHW consumption (gradient)
Line no. Operating line
5450 Gradient end cons
This parameter is used to define the temperature gradient at sensor B38 with which – in
the case of aqua booster operation – the end of consumption is detected. With Aqua
Booster Ge [4765.1], sensor B39 is used for detection (in place of B38).
Line no. Operating line
5451 Gradient start cons keep hot
This parameter is used to define the temperature gradient at sensor B38 from which –
in the case of aqua booster operation – consumption is detected when the Keep hot
function is activated. With Aqua Booster Ge [4765.1], sensor B39 is used for detection
(in place of B38).
Line no. Operating line
5452 Gradient start cons
This parameter is used to define the temperature gradient at sensor B38 from which –
in the case of aqua booster operation – consumption is detected. With Aqua Booster
Ge [4765.1], sensor B39 is used for detection (in place of B38).
Line no. Operating line
5455 Setp readj cons 40°C
Correction value for the setpoint on the LMS14... with a consumption setpoint of
40 °C.
Line no. Operating line
5456 Setp readj cons 60°C
Correction value for the setpoint on the LMS14... with a consumption setpoint of
60 °C.
Gradient end cons
Gradient start cons keep
hot
Gradient start cons
Setp readj cons 40°C
Setp readj cons 60°C