EasyManuals Logo

Siemens LMS14 User Manual

Siemens LMS14
617 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #470 background imageLoading...
Page #470 background image
470/617
Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
6.24 LPB system
The LPB (local process bus) is used as a communication basis for generating a system
with additional ALBATROS
2
controllers or controllers of other manufacture. The system
can be extended at any time.
6.24.1 Address/power supply
Device address and segment address are used as destinations in the bus system
(similar to a postal address). To ensure communication, each device must be correctly
addressed.
Note!
Depending on the type of operator terminal, there is only one LPB address (6600) or
2 separate Device address (6600) and Segment address (6601).
Line no. Operating line
6600 LPB address
S0/G1
S14/G16
Line no. Operating line
6600 Device address
6601 Segment address
The controller’s LPB address is divided into 2 parts each consisting of two 2-digit
numerals.
Example:
14 . 16
Segment number Device number
Note!
Each segment in a system must have a device as a master (device address 1).
In terms of segment address, a differentiation is made between heat source segment
and consumer segments:
0 Heat source segment
1...14 Heat consumer segment
LPB address
Device address and
segment address

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMS14 and is the answer not in the manual?

Siemens LMS14 Specifications

General IconGeneral
BrandSiemens
ModelLMS14
CategoryControl Unit
LanguageEnglish

Related product manuals