6.23.10 Sensor inputs BX
Line no. Operating line
5930
5931
5932
Sensor input BX1, 2, 3, 4
None
DHW sensor B31
Collector sensor B6
DHW circulation sensor B39
Buffer sensor B4
Buffer sensor B41
Flue gas temp sensor B8
Common flow sensor B10
Solid fuel boiler sensor B22
DHW charging sensor B36
Buffer sensor B42
Common return sensor B73
Cascade return sensor B70
Swimming pool sensor B13
Solar flow sensor B63
Solar return sensor B64
Primary exch sensor B26
The sensor input settings assign the appropriate functions.
Note!
Sensor input BX4 is ready assigned to sensor B7. Reading in sensor B7 is safety-
related.
None
Sensor input with no function.
DHW sensor B31
DHW storage tank sensor at the bottom.
Collector sensor B6
This sensor is required for the Solar function.
DHW circulation sensor B39
DHW circulation sensor/standby sensor.
Buffer sensor B4
Buffer storage tank sensor at the top.
Buffer sensor B41
Buffer storage tank sensor at the bottom.
Flue gas temp sensor B8
This sensor is required for flue gas supervision.
Common flow sensor B10
This sensor is required for the common flow.
Sensor input BX1, 2, 3