Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
6.5.32 Floor curing function
Line no. Operating line
HC1 HC2 HC3
850 1150 1450 Floor curing function
Off
Functional heating
Curing heating
Functional/curing heating
Curing/functional heating
Manually
The Floor curing function ensures controlled drying of the floor. It controls the flow
temperature according to a certain temperature profile. Drying of the floor is effected via
the floor heating system and the mixing or pump heating circuit.
Any overtemperatures in the case of pump heating circuits can be prevented by
overtemperature protection (pump cycling) or the temperature limiter.
Note!
In the event of a power failure, the Floor curing function is resumed where operation
had stopped.
Off
Function is deactivated.
Functional heating
The first part of the temperature profile is completed automatically.
Curing heating
The second part of the temperature profile is completed automatically.
Functional/curing heating
The entire temperature profile (first and second part) is completed automatically.
Curing/functional heating
The entire temperature profile (first and second part) is completed automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled
manually.
Warning!
Observe the relevant standards and regulations specified by the floor
manufacturer
Proper functioning is ensured only when the plant is correctly installed
(hydraulic system, electrical installation, settings)! If not observed, the floor
might be damaged
The function can be aborted by selecting Off
Maximum limitation of flow temperature remains active
Floor curing function