6.26 Maintenance/special mode
6.26.1 Maintenance functions
Line no. Operating line
7040 Burner hours interval
When the set number of burner operating hours or burner starts have elapsed, a
maintenance message is displayed. For this message, the number of operating hours
of the burner are counted.
Line no. Operating line
7041 Burner hrs since maintenance
The current value is added up and displayed. On this operating line, the value can be
reset to 0.
Line no. Operating line
7042 Burner start interval
When the set burner start numbers are reached, a maintenance message is displayed.
For this message, the number of starts of the burner are counted.
Line no. Operating line
7043 Burner starts since maint
The current value is added up and displayed. On this operating line, the value can be
reset to 0.
Line no. Operating line
7044 Maintenance interval
Line no. Operating line
7045 Time since maintenance
Line no. Operating line
7050 Fan speed ionization current
This is the fan speed limit from which the burner ionization current maintenance
message should be set if – due to too low ionization current – ionization current
supervision and thus increased speed are activated (only with LMS14...).
Line no. Operating line
7051 Message ionization current
Flag to indicate and reset the burner ionization current maintenance message of the
LMS14... The maintenance message can be reset only if the cause of the message has
been rectified
.
Burner hour's interval
Burner hrs since
maintenance
Burner start interval
Burner starts since maint
Maintenance interval
Time since
maintenance
Fan speed ionization
current
Message ionization
current