Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
6.25.3 Error message functions
These functions can be used to maintain the required flow temperature. If the flow
temperature deviates constantly from the required level for more than the set period of
time, an error message is delivered. If, during an active alarm, the setpoint is
maintained again, the error message is canceled. If, during a DHW charging cycle and
within a parameterized time, the DHW storage tank cannot be charged to at least the
level of the switching differential, an alarm can be set off.
Line no. Operating line
6740 Flow temp 1 alarm
Setting the monitoring time until the error message for heating circuit 1 is delivered.
Error message for heating circuit 1:
Error code 121 Flow temperature heating circuit 1 not reached.
Line no. Operating line
6741 Flow temp 2 alarm
Setting the monitoring time until the error message for heating circuit 2 is delivered.
Error message for heating circuit 2:
Error code 122 Flow temperature heating circuit 2 not reached.
Line no. Operating line
6742 Flow temp 3 alarm
Setting the monitoring time until the error message for heating circuit 3 is delivered.
Error message for heating circuit 3:
Error code 371 Flow temperature heating circuit 3.
Flow temp 1 alarm
Flow temp 2 alarm
Flow temp 3 alarm