Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
Line no. Operating line
2450 Controller delay
Off
Heating mode only
DHW mode only
Heating and DHW mode
Here, you can set the operating mode where the controller delay shall become active.
Off
Function is deactivated.
Heating mode only
Controller delay only acts in Heating mode.
DHW mode only
Controller delay only acts in DHW mode.
Heating and DHW mode
Controller delay acts in Heating and DHW mode.
Note!
During operation of the instantaneous water heater, the controller delay never takes
effect.
Line no. Operating line
2452 Controller delay speed
Speed delivered during the controller delay time.
Line no. Operating line
2453 Controller delay duration
Duration of controller delay. This delay time is started the moment a flame is definitively
detected after ignition.
Controller delay
Controller delay speed
Controller delay
duration