Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Note!
If 2 storage tank sensors are used, the sensor acquiring the higher temperature is
considered.
Caution!
The collector pump is deactivated if one of the storage tank temperatures is
not available (short-circuit or interruption).
Line no. Operating line
2070 Swimming pool temp max
3850 Collector overtemp prot
Menu: Buffer storage tank
4751
Storage tank temp max (buffer storage tank)
Menu: DHW storage tank
5051
Storage tank temp max (DHW storage tank)