369/617
Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Line no. Operating line
[4766.1]
AbsSwitchOffCondAqBo
Off
On
Activation of comparison of absolute temperature values as the final criterion of DHW
consumption.
Line no. Operating line
[4768.1]
Min Keep hot AqBo
Minimum on time of Keep hot function on completion of DHW consumption.
Line no. Operating line
[4769.1]
Interv Burn off time
Interval for Burner off when changing from DHW consumption to the Keep hot function.
Line no. Operating line
[4770.1]
Interv Burn on time
Not in use, not implemented.
Line no. Operating line
[4771.1]
Interv output incr
Period of time on completion of which a change to the next stage of output increase is
made.
Line no. Operating line
[4772.1]
AbsTSwitchOffTresh
Absolute temperature threshold for absolute temperature comparison of outlet
temperature at sensor B38 and inlet temperature at sensor B39 to end the Keep hot
function, if required.
Line no. Operating line
[4773.1]
PumpOverrun AqBo
Not in use, not implemented.
Line no. Operating line
[4774.1]
PumpOver end keep hot
Not in use, not implemented.
Line no. Operating line
[4775.1]
SwitchOnDiff keep hot
Switch-on differential for the Keep hot function.
Line no. Operating line
[4776.1]
SwitchOfDiff keep hot
Switch-off differential for the Keep hot function.