Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
The relay output settings assign the appropriate functions.
None
Relay output with no function.
Circulating pump Q4
The connected pump serves as a DHW circulating pump. Operation of the pump can be
scheduled as required on operating page DHW, operating line Circulating pump release
(1660).
DHW El imm heater DHW K6
Using the connected electric immersion heater, the DHW can be heated according to
operating page DHW storage tank (El imm heater optg mode (5060), El immersion
heater release (5061) and El immersion heater control (5062)).
Warning!
The electric immersion heater must be equipped with a safety limit thermostat!
Note!
El imm heater optg mode (5060) of the electric immersion heater’s operating mode
must be appropriately set.
Collector pump Q5
When using a solar collector, a circulating pump for the collector circuit is required.
Cons circuit pump VK1 Q15
Consumer circuit pump VK1 can be used for an additional consumer. Together with an
external request for heat at input H and configuration Consumer request VK1, an air
heater or similar piece of equipment can be operated.
Boiler pump Q1
The connected pump is used for circulating the boiler water.
Bypass pump Q12
Function is not implemented.
Alarm output K10
The alarm relay signals faults, should they occur. In the event of fault, the relay’s
contact closes after an adjustable Alarm delay (6612). When the fault is corrected, that
is, when the fault status is no longer present, the relay is deenergized with no delay.
The Syst messages alarm relay (6611) setting determines whether or not system errors
signaled via LPB are also capable of triggering the alarm relay.
Note!
If the fault cannot immediately be corrected, it is still possible to reset the alarm relay.
This is made on operating page Faults.
2nd pump speed HC1 Q21
Pump speed 2 for heating circuit 1 is activated.
2nd pump speed HC2 Q22
Pump speed 2 for heating circuit 2 is activated.
2nd pump speed HC3 Q23
Pump speed 2 for heating circuit 3 is activated.