Error
Code
Diag.
Code
Device Display Meaning for the LMV5x System Corrective Action
0D The redundancy contact monitoring function is not permitted
This function is only enabled for the LMV50 and
LMV52. Setting StartReleaseOil to "HT/FG-RedCo" is
not permitted.
0E The COx function is not permitted.
This function is only enabled for the LMV50 and
LMV52. Changing OptgMode COx Gas(Oil) from
"deactivated" is not permitted.
58 Any # Internal communication (µC1 <> µC2)
After initialization, EEPROM page is on ABORT
(last parameterization was possibly interrupted due to a power
failure)
Page number
CRC error of a parameter page
Page number
Page is on ABORT
Page number
Page is on WR_RESTO. A backup restore was made
Page number
Page open too long
Page number
Page has an undefined status
Page number
5F Any #
Parameter Set
damaged
Last backup restore invalid (was interrupted) Repeat parameter set download (from AZL to LMV5)
Fault when copying a parameter page
Number of parameter page
Any # Fault in connection with EEPROM initialization
01 Fault during initialization of EEPROM
02 Number of write attempts exceeded
10 EEPROM was busy when accessed
11 Comparison of EEPROM and RAM area revealed dissimilarity
12 Page area of EEPROM exceeded during write process
13 Access conflict µC1 <> µC2 (arbitration)
Any #
Any #
Internal Fault
Basic Unit
Any #
5B
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
5C
5D
5E
Any #
Any #
5A
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) Check for inductive loads on the outputs.
4) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
Any #
LMV5
60
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
Reset the LMV5
Parameter Set
damaged
59 Any #
Fault with Base Unit (LMV5)
57
Invalid
parameterization
Internal Fault
Basic Unit
61
Parameter
Backup Restore
Section 7 Page 38 SCC Inc.
HOME
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals