Alarm, fault and system messages
11.3 Diagnostics by evaluating the POWER, ETHERNET, STATE/SF LEDs
SIMATIC MV420 / SIMATIC MV440
346 Operating Instructions, 04/2013, A5E02371045-06
11.3 Diagnostics by evaluating the POWER, ETHERNET, STATE/SF
LEDs
LED labeling Meaning How to remedy the problem
GREEN, flashing:
Signals the startup phase after turning
the reader on.
Wait until this is completed and the reader is operational.
POWER
GREEN, lit permanently:
Reader is ready for operation
No error.
Permanently off:
No Ethernet connection to the reader.
Check the connection to the Ethernet cable.
Check whether the connected switch or other
communications partner is operational.
Check or replace the Ethernet cable.
GREEN, permanently on:
An Ethernet connection exists without
data traffic.
To start the user interface of the reader, you also require a
valid network configuration for TCP/IP. Here, you can, for
example, use the Primary Setup Tool to create a valid
network configuration for TCP/IP.
ETHERNET
GREEN flashing:
The reader is exchanging data.
No error.
Off permanently:
The reader is in "Stop" mode (no error)
No error.
GREEN on permanently:
The reader is in RUN mode (no error)
No error.
RED, lit constantly:
The reader is in the "Group error" status
Possible cause when working with onboard
PROFINET IO:
1. Bus error (no physical connection to a
subnet / switch).
2. Wrong transmission speed,
Full duplex transmission is not enabled.
Start the user interface to display the error message. Follow
the suggested remedies, see section "Error messages
(Page 334)".
STATE/SF
RED, flashing
When using onboard PROFINET IO:
1. Bus communication is interrupted.
2. The IP address is incorrect.
3. Bad configuration.
4. Bad parameter assignment.
5. Bad or missing device name.
6. I/O controller does not exist / turned off.
Check whether the IP address or device name occurs
more than once in the network.
Check the settings of the I/O controller.