B Description of the PROFINET Configuration File
289
Commissioning PC Stations - Manual and Quick Start
Release 5/2005
C79000-G8976-C156-07
The AbortConnectionAfter Parameter
This parameter is specified in section [<connectionname>].
The connection name contains the IP address from the iMap project engineering
(network view) and the PROFInet device name configured in iMap.
Parameter Meaning
Syntax [192.11.2.34|S7-300 Station (1)]
AbortConnectionAfter =0
Purpose The parameter specifies whether and after what
waiting time OPC terminates an unused
connection.
Default 0
Possible Values 0 – the OPC server does not terminate the
connection automatically (except when it is closed
down).
Higher than 0 – is interpreted as milliseconds, the
OPC Server terminates the connection as soon as
the connection is no longer used for this period of
time.
Relationship between the Set Protocol-specific
Cycle Times
Since the SIMATIC NET OPC Server can use
variables of different protocols at the same time,
the maximum update rate of the OPC server is the
highest value set for the scan cycle time for the
active protocols (those for which connections are
configured).
Example A scan cycle time of 100 ms is configured for
PROFInet. No other protocol is being used. 100 ms
is used by the OPC server as the minimum update
interval. The S7 protocol is now added and the
scan cycle time configured for this protocol is 500
ms. Result: The OPC Server now uses the value
500 ms as the minimum update interval for all
protocols.

Table of Contents

Other manuals for Siemens SIMATIC NET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET and is the answer not in the manual?

Siemens SIMATIC NET Specifications

General IconGeneral
CategoryIndustrial Communication Software
ManufacturerSiemens
Operating SystemsWindows, Linux
Protocols SupportedPROFIBUS, PROFINET, OPC UA
CompatibilitySiemens PLCs, Third-party devices with supported protocols

Related product manuals