Programming Instructions
R 02/92
Setting of the clock pulse groups (for SS1 module)
Dw
175
Enable for channel 1
Enable for channel 2
DW 176
10’
10°
10’
10°
The lengths of the clock pulse groups in data word DW 176 are given in
BCD
code.
If the enables for channel 1
(DL
175) or channel 2
(DR
175) are set with KH =
FF
the clock pulse
group length for the respective channel is not transferred to the module.
Setting of the hysteresis (for analog submodule)
DW 177
I
Enable for channel 1
I
Enable for channel 2
I
DW 178
10’
10°
10’
10°
The hysteresis values in DW 178 are to be given in
BCD
code.
If the enables for channel 1
(DL
177) or for channel 2
(DR
177) are set with KH =
Ffi
the hysteresis
value for the respective channel is not transferred to the module.
Setting of the rotary axis function
DW 179
Enable for channel 1
Enable for channel 2
If the enables for channel 1
(DL
179) or channel 2
(DR
179) are set with KH =
FE
the rotary axis
function for the respective channel is disabled.