Commissioning
5.5 First commissioning with the AOP30
Converter cabinet units
246 Operating Instructions, 07/2016, A5E03347396A
Note
Selecting the motor type
The selectio
n of the motor type pre-assigns specific motor parameters and optimizes the
operating characteristics and behavior. Details are described in the List Manual in the p0300
parameter.
Note
Selection of a list motor (p0300 ≥ 100)
When a motor type ≥
100 is selected, the article number of the associated motor can be
-down list.
Note
Commissioning of an induction motor
The steps described below also apply to commissioning an induction motor.
ning a permanent-magnet synchronous motor (p0300 = 2), there are a few
special conditions that apply, which are detailed in a separate chapter (see "Setpoint
channel and closed
-loop control/Permanent-magnet synchronous motors").
Entry of the origin for the line contactor
checkback signal: the default setting should
remain
as it is.
Selecting the winding type:
Single winding system
Several separate winding systems or
motors (default setting)
Navigate within the selection fields with <F2>
and <F3>.
Activate your selection with <F5>.
Once you have entered the final value,
choose "Continue" to exit the screen.