Operation
6.11 Communication via EtherNet/IP
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
389
Siemens Drive Object, Instance Number: 32C hex
ass
Get Attribute single
Get Attribute single
Set Attribute single
Table 6- 44 Class Attribute
Table 6- 45 Instance Attribute
p0010: commissioning parameter filter
3 … 18 get STW1 STW1 bit-by-bit access:
Attr. 3 = STW1.0
20 … 35 get ZSW1 ZSW1 bit-by-bit access:
Attr. 20 = ZSW1.0
36 get Actual Frequency Main actual value (actual frequency)
p1120[0]: ramp-function generator ramp-up time
38 get, set Ramp Down Time p1121[0]: ramp-function generator ramp-down
42 get, set OFF3 Ramp Down
p1135[0]: OFF3 ramp-down time
p2200[0]: Technology controller enable
44 get, set PID Filter Time Con-
p2265: Technology controller actual value filter
45 get, set PID D Gain p2274: technology controller differentiation time
p2280: technology controller proportional gain
p2285: technology controller integral time
p2291: technology controller maximum limiting
p2292: technology controller minimum limiting
51 get Output Frequency r0024: output frequency