EasyManua.ls Logo

Siemens SINAMICS G150 - Page 390

Siemens SINAMICS G150
680 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.11 Communication via EtherNet/IP
Converter cabinet units
390 Operating Instructions, 07/2016, A5E03347396A
No.
Service
Name
Value/explanation
53
get
DC Link Voltage
r0026[0]: DC link voltage
54 get Actual Current r0027: current actual value
55
get
Actual Torque
r0031: actual torque value
56 get Output power r0032: active power actual value
57
get
Motor Temperature
r0035[0]: motor temperature
58 get Power Unit Tempera-
ture
r0037[0]: power unit temperature
59
get
Energy kWh
r0039: energy display
60
get
CDS Eff (Local Mode)
r0050: active command data set
61
get
Status Word 2
r0053: status word 2
62
get
Control Word 1
r0054: control word 1
63
get
Motor Speed (Encoder)
r0061: Actual speed value
64
get
Digital Inputs
r0722: Digital inputs status
65
get
Digital Outputs
r0747: digital outputs status
66
get
Analog Input 1
r0752[0]: Analog input 1
67
get
Analog Input 2
r0752[1]: Analog input 2
68
get
Analog Output 1
r0774[0]: Analog output 1
69
get
Analog Output 2
r0774[1]: Analog output 2
70
get
Fault Code 1
r0947[0]: fault number 1
71
get
Fault Code 2
r0947[1]: fault number 2
72
get
Fault Code 3
r0947[2]: fault number 3
73
get
Fault Code 4
r0947[3]: fault number 4
74
get
Fault Code 5
r0947[4]: fault number 5
75 get Fault Code 6 r0947[5]: fault number 6
76
get
Fault Code 7
r0947[6]: fault number 7
77 get Fault Code 8 r0947[7]: fault number 8
78
get
Pulse Frequency
r1801: pulse frequency
79
get
Alarm Code 1
r2110[0]: alarm number 1
80
get
Alarm Code 2
r2110[1]: alarm number 2
81
get
Alarm Code 3
r2110[2]: alarm number 3
82
get
Alarm Code 4
r2110[3]: alarm number 4
83 get PID setpoint Output r2260: technology controller setpoint after ramp-
function generator
84 get PID Feedback r2266: technology controller actual value after
filter
85
get
PID Output
r2294: Technology controller output signal