Note 
Note on FB 18 
If FC 15, FC 16 or FC 18 are called for the same axis in the remainder of the user program, 
the calls must be mutually interlocked. For example, this can be achieved via a common call 
of this function with an interlocked common data interface for the FC 18 parameters. A 
second option is to call the FC 18 repeatedly, whereby the inactive FC 18 will not be 
processed by the program. A multiple-use interlock must be provided. 
The brake test is divided into the following steps: 
 
Brake test sequence 
Step  Expected checkback  Monitoring time value 
Start brake test  DBX 71.0 = 1  TV_BTactiv 
Close brake  Bclosed = 1  TV_Bclose 
Issue travel command  DBX 64.6 Or DBX 64.7  TV_FeedCommand 
Issue test travel command  DBX62.5 = 1  TV_FXSreached 
Wait for hold time  DBX62.5 = 1  TV_FXShold 
Deselect brake test/ 
open brake 
DBX71.0 = 0  TV_BTactiv 
Issue Test O.K.     
Declaration of the function 
FUNCTION_BLOCK FB 11 
 
VAR_INPUT 
  Start   : BOOL ;  //Start of brake test 
  Ack   : BOOL ;  //Acknowledge error 
  Bclosed   : BOOL ;  //Brake closed input (single channel - PLC) 
  Axis   : INT ;  //Testing axis no. 
  TimerNo  : TIMER ;  //Timer from user 
  TV_BTactiv   : S5TIME ;  //TimeValue -> brake test active 
  TV_Bclose   : S5TIME ;  //TimeValue -> close brake 
 TV_FeedComman
d 
: S5TIME  //TimeValue -> force FeedCommand 
  TV_FXSreached  : S5TIME ;   //TimeValue -> fixed stop reached 
  TV_FXShold   : S5TIME ;  //TimeValue -> test brake 
END_VAR 
VAR_OUTPUT 
  CloseBrake   : BOOL ;  //Signal close brake 
  MoveAxis  : BOOL ;  //Do move axis 
  Done   : BOOL ;