Auxiliary Function Output to PLC (H2) 
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0 
2-1 
Detailed Description 
2
2.1  2.1 Predefined auxiliary functions 
2.1.1  Predefined auxiliary functions 
Function 
Predefined auxiliary functions are auxiliary functions for activating system functions. The 
assignment of a predefined auxiliary function to system function cannot be changed. 
During execution of a predefined auxiliary function, the corresponding system function is 
activated and the auxiliary functions are output to the NC/PLC interface. 
Definition of a predefined auxiliary function 
The parameters of a predefined auxiliary function are stored in machine data and can be 
changed in some cases. All parameters of an auxiliary function have the same index. 
•  MD22040 $MC_AUXFU_PREDEF_GROUP[ index ] (group assignment)  
•  MD22050 $MC_AUXFU_PREDEF_TYPE[ index ] (type)  
•  MD22060 $MC_AUXFU_PREDEF_EXTENSION[ index ] (address extension) 
•  MD22070 $MC_AUXFU_PREDEF_VALUE[ index ] (value)  
•  MD22080 $MC_AUXFU_PREDEF_SPEC[ index ] (specification of output behavior)