Detailed description 
  2.12 Block descriptions 
Power Line Basic PLC Program (P3) 
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0 
2-167 
  Signal_5 : BOOL ; 
  Signal_6 : BOOL ; 
  Signal_7 : BOOL ; 
  Signal_8 : BOOL ; 
  Var1 : BYTE ; 
  Var2 : WORD ; 
  Var3 : WORD ; 
 END_STRUCT; 
END_STRUCT; 
BEGIN 
END_DATA_BLOCK 
 
Description of formal parameters 
The table below lists all formal parameters of the Diagnostics function: 
 
Signal  I/O  Type  Value range  Remarks 
Func  I  Int  0, 1, 2  Function  
0: Switch off 
1: Signal recorder 
2: Data trigger 
Parameters for function 1 
Signal_1 to 
Signal_8 
I  Bool    Bit signals checked for change 
NewCycle  I  Bool    See the "Signal recorder" description 
above 
Var1  I  Byte    Additional value 
Var2  I  Int    Additional value 
VAR  I  Int    Additional value 
BufDB  I  Int    Ring buffer DB no. 
ClearBuf  I  Bool    Delete ring buffer DB and reset pointer 
BufAddr 
BufAddr  I/O  Int    Target area for read data 
Parameters for function 2 
DataAdr  I  Pointer    Pointer to word to be tested 
TestVal  I  Word    Comparison value 
AndMask  I  Word    See description 
TestIsTrue  Q  Bool    Result of comparison