Detailed Description   
2.4 Drive service display (for digital drives only) 
  Diagnostic Tools (D1) 
2-20  Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0 
Integrator disabling 
This display indicates whether the speed controller integrator is active. 
 
State 0:  The integrator of the speed controller is enabled. The speed controller functions as a 
PI controller. 
State 1:  Deactivation of the speed controller integrator as requested by the PLC using IS 
"Integrator disable n-controller"  
(DB 31, ... DBX 21.6) is active for the drive module. The speed controller has 
therefore switched from a PI to a P controller. 
Display corresponds to IS "n-controller integrator disabled" 
(DB31, ... DBX93.6). 
References: /FB1/, A2, "Various Interface Signals" 
Setup mode 
Mode display of the SIMODRIVE 611 digital. 
State 0: Normal mode is active for the drive. 
State 1: Setup mode is active for the drive. 
Display corresponds to IS "Setup mode active"  
(DB31, ... DBX92.0). 
References: /FB1/, A2, "Various Interface Signals" 
Parking axis 
Mode display of the SIMODRIVE 611 digital. 
 
State 0:  Axis/spindle in normal mode 
State 1:  Axis/spindle in parking position, i.e. all encoder-specific monitoring and evaluating 
functions are disabled. This allows the encoder to be withdrawn without initiating an 
alarm. 
Setpoint parameter set (drive) 
Indicates which of the 8 drive parameter sets of the SIMODRIVE 611 digital are to be 
activated by the PLC. 
Display corresponds to IS "Parameter set selection A,B,C" 
(DB31, ... DBX21.0 to 21.2). 
References:  /FB1/, A2, "Various Interface Signals" 
Actual parameter set (drive) 
Display indicating which of the 8 drive parameter sets of the SIMODRIVE 611 digital is 
currently active. 
Display corresponds to IS "Active parameter set A,B,C" 
(DB31, ... DBX93.0 to 93.2). 
References: /FB1/, A2, "Various Interface Signals"