Detailed Description 
  2.1 General functionality 
Travel to Fixed Stop (F1) 
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0 
2-19 
Programming FXS in synchronized actions 
The function is not available for analog axes (PLC acknowledgment cannot be awaited). 
Select FXS[ ]=1: 
The following signal interfaces are set: 
Message to PLC: 
IS "Activate travel to fixed stop" (DB31, ... DBX62.4) 
The FXS selection command can only be used in systems with digital drives (VSA, HSA, 
HLA). 
The following condition must be observed: 
MD37060 FIXED_STOP_ACKN_MASK, Bit 0 = 0 
Bit 0 = 1 (waiting for PLC acknowledgment) must not be set, otherwise, an interpolator stop 
would be required to acknowledge the signal, interrupting the movement. 
Deselect FXS[ ]=0: 
The following signal interfaces are reset: 
Message to PLC: 
IS "Activate travel to fixed stop" (DB31, ... DBX62.4) 
The machine parameter: 
MD37060 FIXED_STOP_ACKN_MASK 
must have the value null for signal deselection without motion stop.  
Without ramp 
The torque limit is changed without taking into account the ramp if: 
•  FXS is activated with (FXS[]=1), to make sure that the reduction is activated 
immediately (especially for synchronized actions). 
•  The drive needs to be de-energized as quickly as possible in the event of a fault. 
Selection of FXS with G64 
In the machine parameter: 
MD37060 FIXED_STOP_ACKN_MASK 
bit 0 must be 0 (do not wait for PLC input signal "travel to fixed stop active"), since the 
selection of FXS may not initiate a motion stop.  
Modify the torque FXST 
The clamping torque can already be modified when approaching the stop. 
The torque limit FXST acts in addition to the acceleration limitation with ACC.