Detailed description 
  2.7 Structure and functions of the basic program 
Power Line Basic PLC Program (P3) 
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0 
2-57 
Signal list 
Data block DB 76 is set up when the function is activated. 
A bit is set in the appropriate group in DB 76 for an M signal decoded in the list. 
At the same time, a readin disable is set in the channel in which the M function has been 
output. 
Activation of the function 
The number of groups to be evaluated is specified in basic-program parameter 
ListMGDecGrp. 
The decoding function is activated if this value is between 1 and 16.  
Before activation of decoding, the decoding list DB75 must be transferred to the PLC 
followed by a restart. 
Example 
The table below contains the parameters for the following programming example: 
 
Example parameters 
Group  Decoding list (DB 75)  Signal list 
  Extended  
M address 
First 
M address 
Last 
M address 
in group 
DB 76 
1  2  1  5  DBX0.0 to DBX0.4 
2  3  12  23  DBX2.0 to DBX3.3 
3  40  55  55  DBX4.0