2 control behavior with transient recovery after the absolute value optimum
S49 Priority N (DDC) or H
[0] N (DDC)
1 H
S50 Manual mode with transmitter fault
[0] no switching (display only)
1 manual operation starting with last y
2 manual operation starting with ys
S51 switching manual / automatic via
output switching
[0]
1
2
3
4
Manual key Hi Control signal He Locking He
ES
yes yes / static with
no yes / static with
no switching manual operation
yes yes / dynamic with
yes yes / dynamic without
S52 Iy switch--off in DDC or tracking mode (only K-controllers)
[0] without
1 with
S53 Output variable limit YA / YE
[0] only active in automatic operation
1 active in all operating modes
S54 Output variable display
[0] controller output y
1 position feedback y
R
S55 Direction of control action of the output variable display yAn
[0] normal: yAn = y
1 reversed: yAn = 100% -- y
S56 Assignment of controller variables to the analog output
[0] y0to20mA
1 y4to20mA
2 w0to20mA
3 w4to20mA
4 x0to20mA
13 y2 4to20mA asofversion--B2
14 1--y1 0 to 20 mA as of version --B2
15 1--y1 4 to 20 mA as of version --B2
16 1--y2 0 to 20 mA as of version --B2
17 1--y2 4 to 20 mA as of version --B2