EasyManuals Logo

Siemens Siprotec 7UM611 User Manual

Siemens Siprotec 7UM611
424 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #250 background imageLoading...
Page #250 background image
3 Mounting and Commissioning
250
7UM61 Manual
C53000-G1176-C127-3
Table 3-12 Replacement modules for interfaces
The order numbers of the exchange modules can be found in the Appendix in Section
A.1.
Serial Interfaces
with Bus Capability
For bus-capable interfaces a termination is necessary at the bus for each last device,
i.e. termination resistors must be connected. In the case of the 7UM61, these are vari-
ants with RS485 or Profibus interfaces.
The terminating resistors are located on the RS485 or Profibus interface module,
which is on the B–CPU processor board ((1) in Figure 3-1 and 3-2), or directly on the
p.c.b. of the B_CPU processor PCB (see under margin heading "Processor module
B–CPU", Table 3-2).
Figure 3-7 shows the B–CPU PCB with location of the modules.
The module for the RS485 interface is shown in Figure 3-8, the module for the Profibus
interface in Figure 3-9.
On delivery the jumpers are set so that the termination resistors are disconnected.
Both jumpers of a module must always be plugged in the same way.
Figure 3-8 Position of terminating resistors and the plug-in jumpers for configuration of the
RS485 interface
Interface Mounting Location / Port Replacement module
System interface B
RS232
RS 485
FO 820 nm
Profibus DP RS485
Profibus DP double ring
Modbus RS 485
Modbus 820 nm
DNP3.0, RS 485
DNP 3.0 820 nm
Service interface C
RS232
RS 485
FO 820 nm
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Siprotec 7UM611 and is the answer not in the manual?

Siemens Siprotec 7UM611 Specifications

General IconGeneral
BrandSiemens
ModelSiprotec 7UM611
CategoryRelays
LanguageEnglish

Related product manuals