A.8 Information List
401
7UM61 Manual
C53000-G1176-C127-3
5211 Frequency protection is OFF
(Freq. OFF)
Frequency Prot. AM ON
OFF
* * LED BO 70 181 1 Yes
5212 Frequency protection is
BLOCKED (Freq. BLOCKED)
Frequency Prot. AM ON
OFF
ON
OFF
* LED BO 70 182 1 Yes
5213 Frequency protection is ACTIVE
(Freq. ACTIVE)
Frequency Prot. AM ON
OFF
* * LED BO 70 183 1 Yes
5214 Frequency protection undervolt-
age Blk (Freq UnderV Blk)
Frequency Prot. AM ON
OFF
ON
OFF
* LED BO 70 184 1 Yes
5232 f1 picked up (f1 picked up) Frequency Prot. AM * ON
OFF
* LED BO 70 230 2 Yes
5233 f2 picked up (f2 picked up) Frequency Prot. AM * ON
OFF
* LED BO 70 231 2 Yes
5234 f3 picked up (f3 picked up) Frequency Prot. AM * ON
OFF
* LED BO 70 232 2 Yes
5235 f4 picked up (f4 picked up) Frequency Prot. AM * ON
OFF
* LED BO 70 233 2 Yes
5236 f1 TRIP (f1 TRIP) Frequency Prot. AM * ON m LED BO 70 234 2 Yes
5237 f2 TRIP (f2 TRIP) Frequency Prot. AM * ON m LED BO 70 235 2 Yes
5238 f3 TRIP (f3 TRIP) Frequency Prot. AM * ON m LED BO 70 236 2 Yes
5239 f4 TRIP (f4 TRIP) Frequency Prot. AM * ON m LED BO 70 237 2 Yes
5323 >BLOCK underexcitation protec-
tion (>Exc. BLOCK)
Underexcitation EM * * * LED BI BO
5327 >BLOCK underexc. prot. char. 3
(>Char. 3 BLK.)
Underexcitation EM ON
OFF
**LEDBIBO71531Yes
5328 >Exc. voltage failure recognized
(>Uexc fail.)
Underexcitation EM ON
OFF
**LEDBIBO71541Yes
5329 >BLOCK underexc. prot. char. 1
(>Char. 1 BLK.)
Underexcitation EM ON
OFF
**LEDBIBO71641Yes
5330 >BLOCK underexc. prot. char. 2
(>Char. 2 BLK.)
Underexcitation EM ON
OFF
**LEDBIBO71651Yes
5331 Underexc. prot. is switched OFF
(Excit. OFF)
Underexcitation AM ON
OFF
**LEDBO71551Yes
5332 Underexc. prot. is BLOCKED
(Excit.BLOCKED)
Underexcitation AM ON
OFF
ON
OFF
* LED BO 71 56 1 Yes
5333 Underexc. prot. is ACTIVE (Ex-
cit.ACTIVE)
Underexcitation AM ON
OFF
**LEDBO71571Yes
5334 Underexc. prot. blocked by U<
(Exc. U< blk)
Underexcitation AM ON
OFF
ON
OFF
* LED BO 71 58 1 Yes
5336 Exc. voltage failure recognized
(Uexc failure)
Underexcitation AM * ON
OFF
* LED BO
5337 Underexc. prot. picked up (Exc<
picked up)
Underexcitation AM * ON
OFF
* LED BO 71 60 2 Yes
5343 Underexc. prot. char. 3 TRIP
(Exc<3 TRIP)
Underexcitation AM * ON m LED BO 71 63 2 Yes
5344 Underexc. prot. char. 1 TRIP
(Exc<1 TRIP)
Underexcitation AM * ON m LED BO 71 66 2 Yes
5345 Underexc. prot. char. 2 TRIP
(Exc<2 TRIP)
Underexcitation AM * ON m LED BO 71 67 2 Yes
5346 Underexc. prot. char.+Uexc<
TRIP (Exc<U<TRIP)
Underexcitation AM * ON m LED BO 71 68 2 Yes
5353 >BLOCK overexcitation protec-
tion (>U/f BLOCK)
Overexcitation EM * * * LED BI BO
5357 >Reset memory of thermal
replica U/f (>RM th.rep. U/f)
Overexcitation EM ON
OFF
**LEDBIBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Typ e
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com