PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
8-20 GWA 4NEB 535 2195-02 DS 06
**) Notice
During parameterization with the GSD file, it is possible to select values that are
dependent on each other, but which are not permissible in combination. The
respective parameter is reported as an "Incorrect parameter value" in data set
92.
The following table shows which parameters are dependent on each other and
how these must be set:
Table 8-4: Interdependent parameter settings
Parameter Settings
Rated operating current I
e
Depends on Tripping class CLASS (refer to
Chapter 10.3.2 "Technical Data
Power Unit" on Page 10-12).
Maximum current limit value Greater than Minimum current limit value Chapter
5.4.6 "Specifying Current Limit
Values" on Page 5-27.
Maximum starting time Greater than Starting time Chapter 5.4.3
"Specifying the Starting Mode" on
Page 5-13.
Limiting torque Greater than Start torque Chapter 5.4.3
"Specifying the Starting Mode" on
Page 5-13, torque control and torque
control with current limiting.