2-63
1010ENFM-3B
Section 2
To move the cursor to the desired data function press
To store selection press
Assigning Pgen Output Functions
The Pgen analog output is a buffered TTL-compliant pulse rate signal, similar to the pulse outputs of flow-
meters such as turbines. It varies linearly from 0-5000 Hz in relation to a selected data function.
To assign a function to the Pgen output:
To access the [Pgen] option list press
To move the cursor to the desired data function press
To store selection press
ENT
ENT
2.10.2 RELAY SETUP
Use this menu to assign a function to channel relays. FUE1010EN supports 2 types of relay outputs,
Alarm Relay and Pulse Relay. Alarm Relay outputs operate in “fail-safe” mode. The relay(s) are ener-
gized under normal conditions - an alarm condition causes the relay(s) to de-energize until alarm clears.
The Pulse Relay output supports totalizer and batch relay functions. The output pulse width is approxi-
mately 200 ms; maximum activation rate is 2.5 pulses per second. If totalizer pulses exceed this rate,
excess pulses are stored in overflow register. This allows the relay to “catch up” when flow decreases
enough.
NOTE: Using <F1> Totalizer clear command also clears all channel totalizers plus the overflow
register described in the last paragraph.
Assigning Relay 1 and 2 Functions
FUE1010EN, depending on the model, provides at least two alarm relays. Please refer to the Hardware
Installation Drawing for wiring details. Relays respond to any of the alarm conditions/data functions in-
cluded on the Relay Option List.
PULSE OUTPUT (Pgen Wiring)
FUE1010EN & FUE1010EDN with 1010N-2 Modules
Installation Drawing 1010N-2-7 (Sheet 2 of 2)
PIN# SIGNAL FUNCTION NOTES
11 PGEN 1+ FREQUENCY OUTPUT 1 0 - 5000 Hz, 5 Volt Logic, Square Waveform
12 PGEN 1- REF. GROUND
13 PGEN 2+ FREQUENCY OUTPUT 2
14 PGEN 2- REF. GROUND
TB2
FUE1010EN & FUE1010EDN with Expanded 1010N-7 I/O Modules
Installation Drawing 1010N-7-7 (Sheet 2 of 3)
(Standard, High Performance and Enhanced Performance Flowmeters)
PIN# SIGNAL FUNCTION NOTES
9 PG1 FREQUENCY OUTPUT 1 0 - 5000 Hz, 5 Volt Logic, Square Waveform
10 PG2 REF. GROUND
11 PG3 FREQUENCY OUTPUT 2
12 PG4 REF. GROUND
TB2