2-69
1010ENFM-3B
Section 2
Flow GAL/MIN -2.26
Velocity F/S 0.00
Total KGAL 0.0000
Vs m/s 1273.21
Signal mV 44
Valc % 57
Vaer % 0
Alarm Status ---R-----
AnCal GAL/MIN 0.0000
HiFlow GAL/MIN 1576.8
LoFlow GAL/MIN -1576.8
Siemens 2 Channel [1] SITE1
Current Flow Rate and Units
Flow Data
NOTE: Menu shows English units (i.e., gallons).
Flow This is a real-time (updated) flow rate display in current rate units (e.g., GAL/
MIN).
Velocity F/S Linear flow velocity in f/s and m/s depending on preferred units.
Total This is a real-time (updated) flow total display in current total units (e.g., KGAL).
Vs m/s Current liquid sonic velocity (Vs) in m/s. The Vs value depends on the liquid
and its temperature. This menu cell allows “fine-tuning” when highlighted. Press
the [+] key (coarse adjustment) or the [1] key (fine adjustment) to increase,
or the [-] key (coarse adjustment) or the [2] key (fine adjustment) to decrease
the reading.
CAUTION: Incorrect usage will result in reduced accuracy.
Signal (mV) Xdcr signal strength (in mV). This is the amplitude of the transit-time receive
signals. Improper coupling, attenuative liquid or pipe could cause a low value.
Valc % Input Amplifier gain indication. Larger % indicates a stronger liquid signal.
Vaer % This shows the current percent of aeration detected by the meter.
Alarm Status This letter code field shows the status of the meters built-in alarms. A dash
indicates an inactive alarm. Letter codes reflect the following alarm conditions:
S = Transducer Spacing Warning
E = Empty Alarm
R = Flow Rate Alarm (High or Low rate threshold exceeded)
F = Fault Alarm
A = Aeration Alarm
M = Memory Activated (Fault Suppressed)
K = Makeup Flag (May be Latched)
I = Interface Alarm
P = Pig Alarm (option)
Z = ZeroMatic signal fault
AnCal Flow Rate Simulator for calibrating external devices, etc. Highlight this item
then press the Right Arrow to enable numeric entry. Type desired simulated
flow rate. Be aware of the units prefix (K, M, etc.).
NOTE: AnCal remains active only while you remain in this menu cell.
HiFlow GAL/MIN Most positive expected flow rate for application (adjustable).
LoFlow GAL/MIN Most negative expected flow rate for application (adjustable).
FLOW DATA MENU ITEMS