2-12
1010ENFM-3B
Section 2
2.3.1 HOW TO SELECT A LIQUID CLASS
The liquids listed in the [Liquid Class] option list are representative samples of the class of liquids to
which they belong. Selecting a named liquid fills in the Estimated Vs (m/s), Viscosity (cS), and Density
(SG) parameters automatically. However, you have the option of editing these parameters individually to
fine tune the liquid settings. If you do not find a liquid that matches your application, then you can select
[Other]. This selection will not provide a liquid name or automatic parameter entry. Only Ethylene Glycol
(10, 20, 30, 40 & 50%), CaCl Brine (27%) and all water entries provide energy metering services.
APPLICATION DATA MENU STRUCTURE (continued)
Application Data
Select liquid Sea Water
Toluene
Trichoroethyl
Other
Liquid Class Estimated Vs m/s xxxx (numeric entry)
Viscosity cS x.xx (numeric entry)
Density S.G. x.xxx (numeric entry)
Location Supply
Return
Service Heating
Cooling
Heat Pump
Temperature Range -40F to 450F
-40F to 250F
-40F to 375F
Pipe Configuration Fully Developed*
(Change to Upstream 1 Elbow
Piping) Dbl Elbow +
Dbl Elbow -
Valve
Expander
Reducer
Norm Entry
Header Inlet
Intrusions
Anomaly Diams xxxx (numeric entry)
Ö
Ú
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ú
Ú
Ú
Ú
Ú
Ú
Ú
Ú
Ö
Ú
Ú
*Default
Ú
Ö
Ú
Liquid Class
Siemens 2 Channel [1] 1
Access Liquid Option List
Estimated Vs m/s 1482
Viscosity cS 1.00
Density S.G. 1.000
Select Liquid Water 20C/68F
Use this menu cell to edit the
Estimated Vs ONLY if you are
sure of a more accurate value.
This will reduce the chances of
a re-spacing request for clamp-
on flow transducers during the
install procedure.
Use this menu cell to edit
the liquid viscosity ONLY
if you are certain that the
data you enter is
accurate. An erroneous
entry could affect meter
calibration.
Use this menu cell to
edit the specific
gravity of the liquid.