2-64
1010ENFM-3B
Section 2
To assign functions to Relay 1:
To access the [Relay] option list press
To move the cursor to the desired Relay assignment press
To store selection press
Repeat procedure for Relay 2.
2.10.3 ANALOG INPUT SETUP (optional function)
NOTE: Some versions of the FUE1010EN have the ability to read analog inputs signals. The
[Analog Input Setup] menu cell is not displayed if your model’s operating system does
not include this facility.
The Analog Input Setup function assigns an active analog input to a measurement channel/path. The
meter provides four DC current input ports for single channel units and two DC current input ports for
Dual Channel units. These ports can be assigned to represent supply temperature, return temperature
or power consumption (see table below). The DC current input ranges from a zero level of 4 mA to a full
scale of 20 mA. The [Analog Input Setup] menu cell allows you to enable this port and then span it to any
desired scaling.
ENT
NOTE: Refer to the Installation Drawings or I/O Module markings for the locations of these in-
puts and wiring procedures.
Not Used Not Active
Power Off Power Off alarm occurs when power fails
High Flow Flow rate exceeds high flow setpoint.
Low Flow Flow rate falls below low flow setpoint.
Flow Alarm Flow rate exceeds or falls below flow setpoints.
Fault Alarm System loses receive signal.
Spacing Transducer spacing needs adjusting.
Empty Empty pipe alarm.
Aeration Aeration percentage exceeds alarm setpoint.
Reverse Flow Flow is in negative direction.
BatchTot Batch/Sample total advances.
Pos Total Positive total volume advances by 1 digit.
Neg Total Negative total volume advances by 1 digit.
High Energy High Energy value relay setpoint.
Low Energy Low Energy value relay setpoint.
Energy Postot Positive energy totalizer advances by 1 digit.
Energy Negtot Negative energy totalizer advances by 1 digit.
Td Temperature difference relay setpoint.
Ts Supply temperature relay setpoint.
High CE* High Chiller Efficiency value relay setpoint.
Low CE* Low Chiller Efficiency value relay setpoint.
Soft Fault Fault condition - memory mode active.
*Used with CE Method only. Unit must have Analog Input capability.
RELAY OPTION LIST