213
Technical Data
Battery
Model X3-IES-4K X3-IES-5K X3-IES-6K X3-IES-8K X3-IES-10K X3-IES-12K X3-IES-15K
Battery type Lithium batteries
Battery voltage
range [d.c. V]
160-800
Recommended
battery voltage
[V]
600
Max. charge/
discharge
current [d.c. A]
50
Battery
connection
1
Communication
interface
CAN/RS485
EPS Output
Model X3-IES-4K X3-IES-5K X3-IES-6K X3-IES-8K X3-IES-10K X3-IES-12K X3-IES-15K
EPS peak power
[VA]
2Pn, 10s (Full sun)
Rated EPS
apparent power
[VA]
4000 5000 6000 8000 10000 12000 15000
Nominal EPS
voltage [V]
380/400
Nominal EPS
frequency [Hz]
50/60
EPS rated current
[A]
5.8 7.3 8.7 11.6 14.5 17.4 21.8
Switching time
[s]
< 10ms
Total harmonic
distortion (THDv,
linear load)

3%
Parallel
operation
YES (supporting 10 parallel inverters)
Half wave loads < 2kW