218
Technical Data
• X3-Matebox G2
On-grid inverter
Rated voltage[Vac], frequency[Hz] 380/400/415, 50/60
Max. Grid(INV) apparent power [VA] 16500
Max. Grid(INV) input/ output current[A] 32/25
Off-grid (Inverter)
Rated voltage[Vac], frequency[Hz] 380/400/415, 50/60
Norminal Off-grid(INV) apparent power [VA] 15000
Max. current[A] 25
Grid (Utility)
Rated grid voltage[Vac], frequency[Hz] 380/400/415, 50/60
Max. input/output current[A] 63/25
Load
Rated voltage[Vac], frequency[Hz] 380/400/415, 50/60
Max. current[A] 63
Environment limit
Degree of protection IP65
Protection class Class I
Operating temperature range[°C] -25~+60°C (Derating above +45°C)
Storage temperature[°C] -40~+70°C
Relative humidity[%] 0~100
Altitude[m] <3000
Operating noise [dB]
Normally working < 30; the period when the
switch is automatically adjusted <45
Overvoltage category III(AC), II(DC)
Cooling concept Nature cooling