Instruction Manual
for
AS380 Series Elevator Integrated Drive Controller
130
3 Up peak service: When this function is chosen, system will start up peak service if the up
running elevator from home base has more than three call register at up peak time(set by time
relay or manual switch). At this time all elevators in the system will back to home base as
soon as the completion of response to the hall call and car call. System will recover to normal,
when the up peak time passed (set by time relay or manual switch).
4 Down peak service: When this function is chosen, system will start down peak service if the
down running elevator to the home base has full car situation at down peak time (set by time
relay or manual switch). At this time all elevators in the system will back to highest floor and
standby with door closed as soon as the completion of response to the hall calls and car calls.
System will recover to normal, if the down peak time passed or there is no full car situation
for two minutes.
5 None service floor control function: SMART COMII group control system has preinstall two
service floor schemes for user. User can use two switches to select (or use two time relay to
select). When one of switch set to ON, system will run with the scheme which is set by users.
If both switches are off, elevator will run in normal service floor mode. Each schemes need
preset. Users can appoint which elevator to response hall call at which floors and they can
also appoint elevator to response up call or down call at designated floor.
6 Standard group split function: When the group split mode parameter is set to 0 and the group
split switch is set to ON, group control system split into two independent group control
system in accordance with the preset value.(which elevators belong to group X, which
elevators belong to group Y) When the switch is set to OFF, system is set to normal group
control.
7 Partial incomplete split function: To cope with the inconsistency of bottom floors of elevators
in the group control system, the group dividing mode parameter can be set to 1, and group
should be divided in accordance with the reachable floor (Group Y for the elevator that can
reach the lowest floor, Group X for elevator that can not reach the lowest floor). Turn on the
group dividing switch and the group control system enters into the down-call incomplete split
running mode. At this time, the passengers at the above floor, who want to get to the lowest
floor, can register the down-call signal to elevator that can reach the lowest floor. The system
with activation of incomplete split function will only dispatch the elevator that can reach the
lowest floor to respond. If the down-call from the elevator that can not reach the lowest floor
is registered, system will not activate the incomplete split function and dispatch the easiest
reachable elevator to respond. For the up-call signal, group control system will not make any
split. Meanwhile, to cope with the inconsistency of top floors of elevators in the group
control system, the group dividing mode parameter can be set to 2, and group should be
divided in accordance with the reachable floor (group Y for the elevator that can reach the top
floor, Group X for elevator that can not reach the top floor). Turn on the group dividing
switch and group control system enters into the up-call incomplete split running mode. At
this time, the passengers at the below floor, who want to get to the top floor, can register the
up-call signal to elevator that can reach the top floor. The system with activation of
incomplete split function will only dispatch the elevator that can reach the top floor to
respond. If the up-call from the elevator that can not reach the top floor is registered, system
will not activate the incomplete split function and dispatch the easiest reachable elevator to
respond. For the down-call signal, group control system will not make any split. The
advantage of adoption of such function is to meet the needs of passengers that want to go to
the certain floor while still maintain the running efficiency of group control system.
8 Signal elevator running under special circumstance, if the certain elevator in the group
control system encounter difficult in communication with group control system. The elevator
will automatically switch to signal elevator running mode.
9 Emergency power running modeWhen there is a sudden power cut and need to use back up
power, it is necessary for user to choose this function. Considering the back up powers
limited capacity, system will let the elevator back to home base one by one and standby with
door open. After all the elevator returned to the home base, group control system will assign