CHAPTER ONE - INTRODUCTION
10
SG-System I Operating Manual
1
Approvals
Industry Approvals
The System I meets the following standards:
UL 1610 Central Station Burglar Alarm Units
UL 864 Standard for Fire Alarm System Control Units and Accessories
UL 1635 Digital Alarm Communicator System Units
CAN/ULC-S304-06 Signal Receiving Centre and Premises Burglar Alarm Control Units
CAN/ULC-S559-04 Equipment for Fire Signal Receiving Centres and Systems
EN60950-1:2001 Standard for Information Technology Equipment
AS/NZS 60950.1:2003 Information Technology Equipment - Safety, Part 1: General Requirements
CISPR22 Class B Information Technology Equipment - Radio Disturbance Characteristics - Limits and Methods of Measurements
EN50130-4 Immunity requirements for components of Fire, Intruder, and Social Alarm Systems.
This equipment shall be installed in the USA in accordance with the requirements of NFPA72, NFPA70, and the authority having jurisdic-
tion.
In Canada, the equipment is ULC listed for active communication channel security levels A1~A4 when used in conjunction with T-Link
TL250 and T-Link TL300 Internet/Intranet alarm communicators. For this type of application the supervision and encryption features have
to be enabled. When used in conjunction with digital diallers, the receiver can provide passive communication channel security levels
P1~P3.
For ULC Installations the equipment shall be installed in accordance with the requirements of ULC-S561, ULC-S301 and the authority hav-
ing jurisdiction.
For installations in Japan, the power supply cord must be a PSE / JET Approved Type power cord with a female end type (IEC). It must meet
fully the DENAN Law Category A equipment and be marked with the diamond PSE logo .
UL864 Programming Requirements
NOTE: To all Users, Installers, Authorities having Jurisdiction, and other involved parties. This product incorporates field pro-
grammable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories-
for Fire Alarms Systems, UL 864, certain programming features or options must be limited to specific values or not used at all, as
indicated in the table below.
Table 1: UL864 Programming Requirements
Option number and name
Permitted in
UL 864?
(Y/N)
Possible
settings
Settings
permitted
(UL 864)
Settings
permitted
(ULC)
Option 013: Buzzer Tone N ON/OFF ON ON
Option 020: Mask UPS AC N ON/OFF OFF --
Option 021: Mask UPS BAT N ON/OFF OFF --
Option 024: Mask SG TCP/IP N ON/OFF OFF OFF
Option 025: Mask SG Serial N ON/OFF OFF OFF
Option 028: TCP Printer N ON/OFF OFF OFF
Option 029: Mask Parallel Printer N ON/OFF OFF OFF